Variable Flow
Hydraulically Damped
Overfill Protection Valve
For Above Ground Storage Tanks
+ Alcohols, Biodiesel, Aviation Fuels |
|
|
| |
|
|
|
|
|
|
|
|
|
Press image for
larger view |
|
Press image for
larger view |
|
The Model OFP-3 has been enhanced! Now, the
OFP-3 series of valves not only have the highest flow rating in
their class, the low flow - low pressure characteristics have
been modified to accommodate virtually any delivery truck pump!
These valves have the following flow ratings: |
|
|
|
7 PSI
minimum operating pressure; 10 - 400 GPM. |
|
|
|
Product flow into the tank is shut down completely at any tank
level desired. The level is set by suspending the Float Actuated
Pilot Valve to the desired level in the tank from the provided
Bushing. |
|
|
|
Because of the float - pilot valve actuation system used,
hydraulic shock is minimized. |
| |
|
|
| |
|
|
|
|
|
|
OFP -
FUNCTIONAL TEST KIT |
| |
|
No matter how well
designed, Overfill Protection equipment fails at some
point. To date, the only means to test the shutdown
function of these valves in the field was to fill the
tank above the equipment’s shut-off level. The OFP
Functional Test Kit is the answer! Available as an
option for new Vmι
OFP-2 and OFP-3 installations, and available as a
retrofit kit for Vmι
installed equipment. Contact factory or visit our web
site for full description and installation instructions. |
| |
| |
|
|
Press image for
larger view |
|
|
|
Designed and Manufactured in U.S.A. |
|
|
| |
|
SPECIFICATIONS
& COMPONENTS |
| |
|
Meets Uniform Fire Code
(August, 1994), Article 79 Flammable and Combustible Liquids:
"shut off the flow into the tank at 90% of capacity" and "means
shall be provided to empty the fill hose into the tank after the
automatic shut-off device is activated." Installation
instructions provide plumbing details and optional parts to
complete this style of installation, additional part OFP-1030
required. |
| |
|
Meets NFPA code 30A
requirements for completely stopping
the flow of fuel into the tank at 98% fuel level. |
| |
|
CARB tested .
Does not affect Stage 2 vapor recovery. |
| |
|
FLOW RATE:
PSI flow requirements at valve: 7
PSI minimum operating pressure; 10 - 400 GPM depending on pump capability.
Flow rates into the tank are reflective of pump performance and piping
restrictions. A tanker truck equipped with a medium age ("good condition"),
three inch positive displacement pump, filling an AST through an OFP-3, through
12 feet of three inch flexible hose and an OFP-3 with a 3" drop tube will flow
236 GPM @ 10 PSI, (observed field results). |
|
|
|
CAUTION:
Any fuel delivery pump, pumping fuel into
a tank system equipped with an automatic shutdown device, must have a
functioning pressure relief. Vaporless Manufacturing Inc. recommends 30 PSI (PTO
or other) pressure relief. |
|
|
|
FUEL:
|
● |
Gasoline,
100% methanol*, 100% ethanol*, up to 15% MTBE |
| |
● |
Any
combination of the above |
| |
● |
#1 or #2
diesel, kerosene, Jet A* or JP-4*, AV Gas*, and
Biodiesel* |
| |
|
|
* |
When
used with Biodiesel over 5%, any
alcohol fuel concentration above 20%, Jet A,
JP-4 or AV Gas, |
| |
order part # OFP3-SSVS for
stainless steel fittings and stainless steel
vent tubing. For chemical applications other
than listed above, contact factory. |
|
|
|
|
|
COMPONENTS:
OFP Valve - 12 1/2" high, 9 1/4"
wide, inlet 3" male NTP; discharge 3" female NTP; Pilot Valve
and Float Assembly fit through 4" threaded opening. Bushing for
tank bung installation provided - 4" or 6", see 3/1 and 3/2
below. The Pilot Valve is connected to the Bushing with Steel
Bite (compression) fittings and steel tubing. Steel tubing
(2-22" lengths provided) is cut to length at installation to
provide compatibility with local regulation and tank size. UL
listed compression fittings and tubing provided. |
|
|
|
COMPONENT OPTIONS:
Part #OFP3-SSVS: Provides Stainless Steel Fittings
and Stainless Steel Tubing for the
OFP-3\1 and OFP-3\2 Valve when used with
Biodiesel concentrations above 5%, Ethanol and Methanol
concentrations above 20% and for Jet A, JP-4 and Aviation Gas.
Part #SS-113:
Additional Stainless Steel Tubing
for use with OFP3-SSVS when installing an OFP-3\2. Available by
the foot. |
|
|
|
MODEL 3\1: One six
inch tank opening required, OFP Valve and Pilot Valve mount on
6" male pipe thread Bushing provided. For use with 3" drop tube
only. |
|
|
|
MODEL 3\2:
Requires two tank bungs.
Combinations of : 2 - 4" bungs or 1 - 3" bung and 1 - 4" bung.
Consult factory for other combination or custom configurations.
One 4" male NPT Bushing provided to install Pilot Valve and to
vent OFP Valve. For use with 3" drop tube only. |
|
|
|
OPERATION |
| |
| TANK FILLING:
When AST filling operation begins, (fuel in the AST is below the
level of the Pilot Valve, no pressure in fuel delivery line) the
OFP Valve is in the closed position. The filling operation
pressurizes the tubing from the inlet of the OFP Valve, through
the Bushing to the Pilot Valve. Pressure continues from the
pilot valve back through the second tubing, through the Bushing,
entering the area under the piston of the OFP Valve. The piston
is forced up, allowing tank to fill. Air above the piston is
forced through the vent tubing to the Bushing, into the tank
top. When the piston is raised, fuel will flow into the AST. |
| |
| SHUT OFF:
As product in the tank rises, it engages the Float Assembly.
When the Float rises to the predetermined fill level, a poppet
is closed in the Pilot Valve. The closed poppet shuts off flow
and pressure through the Pilot Valve. Without pressure to keep
the piston in the open position, the piston resets to the closed
position. Plumbing diagram and fittings needed to clear
fuel left in the delivery hose after a shut-down are shown in
the installation diagram. |
| |
| Plumbing diagram and fittings
needed to clear fuel left in the delivery hose are shown in the
installation diagram. |
| |
|
WARRANTY
INFORMATION |
| |
| Equipment
is warranted to be free from defects in materials and workmanship for a period
of eighteen (18) months from date of installation (see Warranty Card for
details). |
|
|
|