Overfill Protection
Valve
For Above
Ground Storage Tanks |
|
| |
|
| |
|
|
|
|
|
|
+
Alcohols, Biodiesel
and Aviation Fuels |
|
| |
|
| |
|
| |
|
|
|
|
|
Press photos for larger image |
|
|
| |
|
|
|
Smaller is better. To prove it,
Vmι
introduces the OFP-2 series
of overfill protection valves. Higher flow rates with less
pressure (See Flow Rates). Overall height of main valve is three
inches shorter, allowing it to fit in virtually any spill
containment pan. |
|
|
|
OFP - Functional Test Kit* |
|
|
| |
|
|
|
|
|
| FLOW
RATES: |
Highest in Class |
| |
|
140 GPM @ 30 PSI: CAUTION: The delivery
truck pump must be equipped with a functioning pressure
relief valve.
Vmι
recommends not
exceeding 30 PSI delivery pressure. The hydraulic shock
of an overfill shut-off may damage connecting hoses if
excessive pressure is used. |
|
|
|
One Valve, Any Tank:
Product flow into
the tank is shut down completely at any tank level
desired. The shut down level is set by suspending the
Float Actuated Pilot Valve to the desired level in the
tank from the tank top. |
|
|
|
Fuels:
|
●
|
|
Gasoline, 100% methanol**, 100%
ethanol**, up to 15% MTBE |
|
● |
|
Any combination of the above |
●
|
|
#1 or #2 diesel, kerosene, Jet A** or JP-4**, AV
Gas**, and Biodiesel** |
|
|
|
|
**When used with Biodiesel
over 5%, any alcohol fuel concentration above
20%, Jet A, JP-4 or AV Gas, order part # OFP2-SSVS for
stainless steel fittings and stainless steel vent
tubing. For chemical applications other than those
listed above, contact factory. |
|
|
Press
Photo for larger image |
|
|
 |
|
|
|
|
| |
|
F UNCTIONAL
TEST KIT |
|
|
|
| |
No matter how well designed, Overfill
Protection equipment fails at some point. To date, the
only means to test the shutdown function of these valves
in the field was to fill the tank above the equipment’s
shut-off level. The OFP Functional Test Kit is the
answer! Available as an option for new
Vmι
OFP-2 and OFP-3 installations, and available as a
retrofit kit for
Vmι
installed equipment. Contact factory or visit our web
site for full description and installation instructions. |
|
|
|
|
|
S PECIFICATIONS
&
COMPONENTS |
| |
| |
●
|
Meets Uniform Fire
Code (August, 1994), Article 79 Flammable
and Combustible Liquids: "shut off the flow into the tank at 90% of capacity"
and "means shall be provided to empty the fill hose into the tank after the
automatic shut-off device is activated." Installation instructions provide
plumbing details to complete this style of installation, additional part,
OFP-1030 required. |
|
|
|
|
| |
● |
Meets NFPA code 30A
requirements for complete shutdown @ 98% fuel level. |
|
|
|
|
| |
● |
CARB tested:
Does not affect Stage 2 vapor recovery. |
|
|
|
|
| |
FUELS: |
| |
|
| ● |
Gasoline, 100% methanol*, 100% ethanol*, up to
15% MTBE |
|
| ● |
Any combination of the above |
|
| ● |
#1 or #2 diesel, kerosene, Jet A* or JP-4*, AV
Gas*, and Biodiesel* |
|
|
| |
|
|
| |
|
*When used with Biodiesel over
5%, any alcohol fuel concentration above 20%, Jet
A, JP-4 or AV Gas, order part # OFP2-SSVS for stainless
steel fittings and stainless steel vent tubing. For
chemical applications other than those listed above,
contact factory. |
| |
|
|
| |
COMPONENTS:
Shut-off Valve- 5
1/4" high, 4 1/4" wide, 2" female pipe threads in and 2"
female pipe threads out; Pilot Valve and Float Assembly
fits through a 4" pipe bung; Steel Bite (compression)
fittings and steel tubing (two - 22" lengths) provided
(cut to length in field) for mounting Pilot Valve;
Bushing provided, 4" - 2\1 and 2\2 model, see 2\1 and
2\2 description below; U.L. listed compression fittings
for copper tubing provided. Not provided; copper tubing,
pipe nipples and pipe fittings, dry break\quick
disconnect connectors. |
|
|
|
|
|
COMPONENT OPTIONS:
Part
#OFP2-SSVS: Provides Stainless Steel Fittings and
Stainless Steel Tubing for the OFP-2\1 and OFP-2\2 Valve
when used with Biodiesel concentrations above 5%,
Ethanol and Methanol concentrations above 20% and for
Jet A, JP-4 and Aviation Gas.
Part #SS-113:
Additional Stainless Steel Tubing for use with OFP2-SSVS
when installing an OFP-2\2. Available by the foot. |
|
|
|
| |
Model 2\1:
One 4" tank
opening required. Shutdown Valve and Pilot Valve mount
on a 4" x 2" male pipe thread bushing (provided). For
use with 2" drop tube only. |
|
|
|
| |
Model 2\2:
Requires two tank
openings; one opening may be 2" or 3" and the second
opening should be 4" (two 4" openings are acceptable).
4" pipe thread bushing provided. Requires a minimum of
one 2" and one 4" opening. |
|
|
|
| |
CAUTION:
Any fuel delivery
pump, pumping fuel into a tank system equipped with an
automatic shut-down device, must have a functioning
pressure relief. Vaporless Manufacturing Inc. recommends
30 PSI relief pressure setting. |
|
| |
|
WARRANTY
INFORMATION |
| |
| |
Equipment
is warranted to be free from defects in materials and workmanship for a period
of eighteen (18) months from date of installation (see Warranty Card for
details). |
|
| |
|
|
|