Fuel Transfer Controllers |
|
|
|
|
|
Site Transfer Pump Controller • Two Level -
Overfill Protection |
| |
|
|
| |
|
| |
|
|
High Level Warning |
|
| |
|
|
●
|
Shut-down & Alarm |
|
|
|
|
|
High Level Alarm |
|
|
|
|
|
|
● |
Shut-down & Lockout |
| |
|
|
| |
|
|
| |
|
|
| |
|
|
|
Full Flow, |
|
|
|
|
|
No Valve Restrictions! |
| |
|
|
|
No Hydraulic Hammer! |
| |
|
|
|
Notification and Protection! |
| |
|
|
|
|
Ability to Empty Hose from Delivery
Tanker |
|
|
|
|
and Pipe to Storage Tank after 1st High Level
Warning! |
|
|
|
Enclosure meets or exceeds U.L. Class 1, Group D
hazardous environment criteria. |
|
|
|
Regulatory Codes require
Overfill Protection for all fuel storage tanks. The flow of fuel
into a tank must be "automatically shut-off".
Additionally, regulatory codes require, and common sense
dictates, you provide a means to empty the transfer hose between
the supply tank and the transfer pump. The
Vmι
AST-4010 and AST-4012 Fuel Transfer Controllers provide this
with no flow restriction. |
|
|
|
The AST-4010 provides
overfill protection for a single tank that uses a site mounted,
motor starter driven, electric transfer pump. The AST-4012
provides overfill protection for two tanks having a common
delivery line, using a single site mounted, motor starter
driven, electric transfer pump. |
|
|
 |
|
|
| |
|
|
This device may be
covered by one or more patent applications
- Designed and Manufactured in U.S.A. |
|
|
|
|
Regulatory Compliance -
Empty Transfer Hoses |
|
|
|
Uniform Fire Code
and NFPA Code 30 states, "for rigid hose delivery systems, an
approved means must be provided to empty the fill hose into the
tank after the automatic shut-off device is activated". The
Vmι
AST-4010 and AST-4012 provide full pump capacity to empty the
hose after High Level shut-off, no restrictions! |
|
|
|
Controls Motors Up To 25 HP |
|
|
|
For use with 120 to
440 volts, single phase or 3 phase motors. Installation
instructions have wiring information and illustrations. Contact
factory for larger motor controls. |
|
|
|
Alarm Circuit / Alarm Relays |
|
|
|
Uses audible and/or
visual alarms in addition to shut-off!
Intrinsically Safe, High Level and High Alarm sensor inputs
provided. Wiring instructions provided for single-dual level
sensor, or for two single level sensors. |
|
|
|
Operation Description |
|
|
|
Normally closed,
single point sensors are set at two levels in the tank. During
filling operations the START-JOG switch is used to start the
fuel transfer. The STOP-RESET Switch is used to stop operations
when fuel has been delivered.
If during fueling operations, fuel reaches the first sensor,
"High Level", the pump motor will automatically shut-off. The
alarm circuit will be activated providing notification of
shut-off. The alarm will be silenced by operation of the
STOP-RESET switch. The operator should change the valves on the
delivery vehicle to enable the pump, when restarted, to pull
from an empty compartment. Turning and holding the START-JOG
switch restarts the pump, emptying the delivery hose. Fuel
transfer will stop upon release of the START-JOG switch. Should
the operator ignore the "High Level" warning and continue
filling the tank, the second "High Alarm" sensor will shut-off
the pump before an overfill can occur. At this point, the pump
will not start again until the fuel level drops below High Alarm
sensor. |
|
|
|
Enclosure Meets or Exceeds U.L. Class 1, Group D
Hazardous Environment Criteria |
|
|